DQRID : D011206.7
Start DateStart TimeEnd DateEnd Time Data Quality Metric
06/01/2000000002/21/20011701Incorrect
more
Subject:
SGP EBBR E25 - E25 EBBR Soil Heat Flow #1 Incorrect
DataStreams:sgp30ebbrE25.b1, sgp15ebbrE25.b1
Description:
The #1 soil heat flow sensor developed a +60 W m-2 bias
and thus indicated higher soil heat flows than the other
sensors.  This results in slightly higher sensible and latent heat
fluxes than is correct. The sensor was replaced on 2/21/01.
Suggestions: 
Measurements:sgp15ebbrE25.b1:
  • soil_heat_flow_1_mv
more
sgp30ebbrE25.b1:
  • latent_heat_flux
  • surface_soil_heat_flux_avg
  • soil_heat_flow_1
  • surface_soil_heat_flux_1
  • sensible_heat_flux
  • corr_soil_heat_flow_1
more