Data Quality Reports for Session: 122062 User: perez Completed: 08/26/2009


TABLE OF CONTENTS

DQR IDSubjectData Streams Affected
D031020.1SGP/SIRS/E1 - failed SIRS multiplexersgpsirs20sE1.a0, sgpsirsE1.00, sgpsirsE1.b1
D031118.1SGP/SIRS/E1 - Unknown - Downwelling shaded longwave measurement incorrectsgpsirs20sE1.a0, sgpsirsE1.00, sgpsirsE1.b1


DQRID : D031020.1
Start DateStart TimeEnd DateEnd Time
10/14/2003202310/21/20031930
Subject:
SGP/SIRS/E1 - failed SIRS multiplexer
DataStreams:sgpsirs20sE1.a0, sgpsirsE1.00, sgpsirsE1.b1
Description:
Beginning 10/14, a failed multiplexer resulted in missing 
                  downwelling shortwave data and downwelling and upwelling 
                  longwave data which were much too low. The multiplexer 
                  handles data for the longwave instruments (UIR and DIR) 
                  case and dome temperatures as well as the downwelling shortwave 
                  hemispheric instrument (DS).
Measurements:sgpsirs20sE1.a0:
  • Instantaneous Downwelling Pyrgeometer Dome Thermistor Resistance, Shaded
    Pyrgeometer(inst_down_long_shaded_dome_resist)
  • Instantaneous Downwelling Pyrgeometer Case Thermistor Resistance, Shaded
    Pyrgeometer(inst_down_long_shaded_case_resist)
  • Instantaneous Downwelling Hemispheric Shortwave, Unshaded Pyranometer Thermopile
    Voltage(inst_global)
  • Instantaneous Upwelling Pyrgeometer Dome Thermistor Resistance, Pyrgeometer(inst_up_long_dome_resist)
  • Instantaneous Upwelling Pyrgeometer Case Thermistor Resistance, Pyrgeometer(inst_up_long_case_resist)

sgpsirsE1.b1:
  • Downwelling Longwave Hemispheric Irradiance, Shaded Pyrgeometer, Minima(down_long_hemisp_shaded_min)
  • Instantaneous Case Temperature(inst_up_long_case_temp)
  • Instantaneous Downwelling Pyrgeometer Case Thermistor Temperature, Shaded
    Pyrgeometer(inst_down_long_shaded_case_temp)
  • Downwelling Shortwave Hemispheric Irradiance, Ventilated Pyranometer, Maxima(down_short_hemisp_max)
  • Upwelling (10 meter) Longwave Hemispheric Irradiance, Pyrgeometer, Minima(up_long_hemisp_min)
  • Instantaneous Downwelling Pyrgeometer Dome Thermistor Temperature, Shaded
    Pyrgeometer(inst_down_long_shaded_dome_temp)
  • Downwelling Shortwave Hemispheric Irradiance, Ventilated Pyranometer, Standard
    Deviation(down_short_hemisp_std)
  • Downwelling Longwave Hemispheric Irradiance, Shaded Pyrgeometer, Maxima(down_long_hemisp_shaded_max)
  • Downwelling Shortwave Hemispheric Irradiance, Ventilated Pyranometer, Minima(down_short_hemisp_min)
  • Upwelling (10 meter) Longwave Hemispheric Irradiance, Pyrgeometer(up_long_hemisp)
  • Downwelling Longwave Hemispheric Irradiance, Shaded Pyrgeometer(down_long_hemisp_shaded)
  • Instantaneous Dome Temperature(inst_up_long_dome_temp)
  • Upwelling (10 meter) Longwave Hemispheric Irradiance, Pyrgeometer, Maxima(up_long_hemisp_max)
  • Upwelling (10 meter) Longwave Hemispheric Irradiance, Pyrgeometer, Standard
    Deviation(up_long_hemisp_std)
  • Down-welling unshaded pyranometer voltage(down_short_hemisp)
  • Downwelling Longwave Hemispheric Irradiance, Shaded Pyrgeometer, Standard
    Deviation(down_long_hemisp_shaded_std)

sgpsirsE1.00:
  • null(Raw data stream - documentation not supported)


Back To Table of Contents

DQRID : D031118.1
Start DateStart TimeEnd DateEnd Time
11/11/2003043811/18/20032200
Subject:
SGP/SIRS/E1 - Unknown - Downwelling shaded longwave measurement incorrect
DataStreams:sgpsirs20sE1.a0, sgpsirsE1.00, sgpsirsE1.b1
Description:
Downwelling longwave values were very noisy and out of range 
               due to a missing PIR case temperature measurement. Faulty 
               wiring to the case temperature thermistor on the downwelling 
               longwave IR instrument (PIR) was the likely cause of
               the problem.
               On 11/18, the E1 tracker and associated instruments (direct 
               shortwave -NIP, hemispheric shaded shortwave -8-48 and 
               hemispheric shaded longwave - problem PIR) were moved to a new 
               tracker stand.  Rewiring the instrument corrected the problem.
Measurements:sgpsirs20sE1.a0:
  • Instantaneous Downwelling Pyrgeometer Case Thermistor Resistance, Shaded
    Pyrgeometer(inst_down_long_shaded_case_resist)

sgpsirsE1.b1:
  • Downwelling Longwave Hemispheric Irradiance, Shaded Pyrgeometer, Minima(down_long_hemisp_shaded_min)
  • Downwelling Longwave Hemispheric Irradiance, Shaded Pyrgeometer(down_long_hemisp_shaded)
  • Instantaneous Downwelling Pyrgeometer Case Thermistor Temperature, Shaded
    Pyrgeometer(inst_down_long_shaded_case_temp)
  • Downwelling Longwave Hemispheric Irradiance, Shaded Pyrgeometer, Maxima(down_long_hemisp_shaded_max)
  • Downwelling Longwave Hemispheric Irradiance, Shaded Pyrgeometer, Standard
    Deviation(down_long_hemisp_shaded_std)

sgpsirsE1.00:
  • null(Raw data stream - documentation not supported)


Back To Table of Contents



END OF DATA