DQR ID | Subject | Data Streams Affected |
---|---|---|
D100203.2 | NSA/TWR/C1 - 40m level data incorrect | nsatwrC1.b1 |
D110722.3 | NSA/MET/C1 - 20m T/RH sensor failure | nsatwrC1.b1 |
Start Date | Start Time | End Date | End Time |
---|---|---|---|
12/09/2009 | 2316 | 07/18/2011 | 0002 |
Subject: | NSA/TWR/C1 - 40m level data incorrect |
DataStreams: | nsatwrC1.b1 |
Description: | A power distribution problem required us to turn off the 50V DC power to the 40m level. This shutdown the T/RH probe and the heating of the ultrasonic sensor. The wind data is useful at times when there is no icing present. This DQR is a follow on to D091201.2 that was closed when the 20m level T/RH probe was replaced. |
Measurements: | nsatwrC1.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
11/21/2010 | 1100 | 07/20/2011 | 1823 |
Subject: | NSA/MET/C1 - 20m T/RH sensor failure |
DataStreams: | nsatwrC1.b1 |
Description: | The 20m temperature and RH were erratic and incorrect resulting in incorrect vapor pressure calculations. The sensor was damaged by voltage spikes on the power lines. |
Measurements: | nsatwrC1.b1:
|