DQR ID | Subject | Data Streams Affected | Data Quality Metric |
---|---|---|---|
D140529.1 | MAO/ECOR/M1 - CO2/H2O Means, CO2 flux, and Latent Heat Flux Incorrect | mao30ecorM1.b1 | Incorrect |
D140529.2 | MAO/ECOR/M1 - Wind Direction Too Low by About 10 Degrees. | mao30ecorM1.b1 | Incorrect |
D140625.1 | MAO/ECOR/M1 - Fluxes and wind measurements incorrect. | mao30ecorM1.b1 | Incorrect |
D140825.3 | MAO/ECOR/M1 - Latent Heat Flux and CO2 Flux Incorrect | mao30ecorM1.b1 | Incorrect |
D140905.1 | MAO/ECOR/M1 - Data Missing | mao30ecorM1.b1 | Missing |
D150105.1 | MAO/ECOR/M1 - All Data Missing | mao30ecorM1.b1 | Missing |
D150402.3 | MAO/ECOR/M1 - Missing Data | mao30ecorM1.b1 | Missing |
D150512.1 | MAO/ECOR/M1 - Latent Heat Flux and Water Vapor Density Incorrect | mao30ecorM1.b1 | Incorrect |
Start Date | Start Time | End Date | End Time | Data Quality Metric |
---|---|---|---|---|
04/03/2014 | 1800 | 05/21/2014 | 1400 | Incorrect |
Subject: | MAO/ECOR/M1 - CO2/H2O Means, CO2 flux, and Latent Heat Flux Incorrect |
DataStreams: | mao30ecorM1.b1 |
Description: | All CO2 and water vapor means, CO2 flux, and latent heat flux are incorrect for the period. |
Measurements: | mao30ecorM1.b1:
|
Start Date | Start Time | End Date | End Time | Data Quality Metric |
---|---|---|---|---|
04/03/2014 | 1800 | 05/22/2014 | 1530 | Incorrect |
Subject: | MAO/ECOR/M1 - Wind Direction Too Low by About 10 Degrees. |
DataStreams: | mao30ecorM1.b1 |
Description: | ECOR wind direction was about 10 degrees low during this period. |
Measurements: | mao30ecorM1.b1:
|
Start Date | Start Time | End Date | End Time | Data Quality Metric |
---|---|---|---|---|
06/21/2014 | 0130 | 06/21/2014 | 1400 | Incorrect |
Subject: | MAO/ECOR/M1 - Fluxes and wind measurements incorrect. |
DataStreams: | mao30ecorM1.b1 |
Description: | The measurements were incorrect because the ECOR tripod was tipped over. |
Measurements: | mao30ecorM1.b1:
|
Start Date | Start Time | End Date | End Time | Data Quality Metric |
---|---|---|---|---|
06/21/2014 | 0130 | 08/24/2014 | 1500 | Incorrect |
Subject: | MAO/ECOR/M1 - Latent Heat Flux and CO2 Flux Incorrect |
DataStreams: | mao30ecorM1.b1 |
Description: | The analog outputs of the H2O/CO2 analyzer were not working; therefore latent heat flux and CO2 flux were incorrect during the specified period. |
Measurements: | mao30ecorM1.b1:
|
Start Date | Start Time | End Date | End Time | Data Quality Metric |
---|---|---|---|---|
08/27/2014 | 1200 | 08/28/2014 | 2030 | Missing |
Subject: | MAO/ECOR/M1 - Data Missing |
DataStreams: | mao30ecorM1.b1 |
Description: | All data was missing during then stated period. |
Measurements: | mao30ecorM1.b1:
|
Start Date | Start Time | End Date | End Time | Data Quality Metric |
---|---|---|---|---|
12/22/2014 | 1300 | 12/24/2014 | 1400 | Missing |
Subject: | MAO/ECOR/M1 - All Data Missing |
DataStreams: | mao30ecorM1.b1 |
Description: | All data missing because of a broken sonic breakout box wire lead. |
Measurements: | mao30ecorM1.b1:
|
Start Date | Start Time | End Date | End Time | Data Quality Metric |
---|---|---|---|---|
01/20/2015 | 0800 | 03/27/2015 | 2200 | Missing |
Subject: | MAO/ECOR/M1 - Missing Data |
DataStreams: | mao30ecorM1.b1 |
Description: | All data missing for the stated period. |
Measurements: | mao30ecorM1.b1:
|
Start Date | Start Time | End Date | End Time | Data Quality Metric |
---|---|---|---|---|
04/05/2015 | 1900 | 05/11/2015 | 1630 | Incorrect |
Subject: | MAO/ECOR/M1 - Latent Heat Flux and Water Vapor Density Incorrect |
DataStreams: | mao30ecorM1.b1 |
Description: | Latent heat flux was incorrect because the water vapor density was not being correctly measured. |
Measurements: | mao30ecorM1.b1:
|