DQRID : D941208.2
Start DateStart TimeEnd DateEnd Time Data Quality Metric
11/15/1994230011/30/19941600Suspect
more
Subject:
SGP/EBBR/E7 - Radiation Shield Problem
DataStreams:sgp5ebbrE7.b1, sgp30ebbrE7.b1
Description:
The right radiation shield was out of position or off during the period of
time indicated.  This may or may not have occurred as a result of preventative
maintenance on November 15.  All air and humidity probe temperatures (except
the reference temperature), relative humidities, vapor pressures, Bowen ratio,
sensible heat flux, and latent heat flux during this period are questionable.
During a large part of the period the resultant sensible and latent heat fluxes
look reasonable.  However, during part of the period, the difference in
relative humidity between the two EBBR levels appears to be much too large.
Unusual differences in temperatures are not as obvious.
Suggestions: 
Measurements:sgp5ebbrE7.b1:
  • vapor_pressure_bottom
  • vapor_pressure_top
  • rh_bottom_fraction
  • temp_air_bottom
  • rh_top_fraction
  • temp_trh_top
  • temp_trh_bottom
  • temp_air_top
more
sgp30ebbrE7.b1:
  • vapor_pressure_top
  • latent_heat_flux
  • temp_trh_top
  • temp_air_bottom
  • bowen_ratio
  • temp_air_top
  • rh_bottom_fraction
  • vapor_pressure_bottom
  • temp_trh_bottom
  • rh_top_fraction
  • sensible_heat_flux
more