Subject: | SGP/EBBR/E15 - Reprocess: Sensible and Latent Heat Fluxes, Soil Set #2 Sometimes Incorrect |
DataStreams: | sgp30ebbrE15.b1
|
Description: | Spikes in soil set #2 sometimes caused sensible and latent heat fluxes to be incorrect.
There is no electronic connection between the soil set #2 sensors, so it is suspected that
there was a problem in the soil set #2 cable bundle. A power outage ensued, after which
the soil set #2 problem did not re-occur. |
Suggestions: | Use soil sets 1, 3, 4, and 5 to determine an average soil heat flow. Re-calculate
sensible and latent heat flux from the equations in the EBBR handbook. |
Measurements: | sgp30ebbrE15.b1: - soil_moisture_2
- surface_soil_heat_flux_2
- surface_soil_heat_flux_avg
- energy_storage_change_2
- soil_temp_2
- soil_heat_capacity_2
- latent_heat_flux
- corr_soil_heat_flow_2
- soil_heat_flow_2
- sensible_heat_flux
more
|