DQRID : D030115.2
Start DateStart TimeEnd DateEnd Time
08/16/2002172012/10/20021720
more
Subject:
SGP/EBBR/E12 - Reprocess: Net Rad Calibration Coefficients
DataStreams:sgp5ebbrE12.b1, sgp30ebbrE12.b1
Description:
The Net Radiometer coefficients were incorrect in the CR10
program when the replacement EBBR unit was installed on
08/16/02.

The data can be easily corrected; see the Suggestion area below.
Suggestions: 
Positive net radiation measurements must be multiplied by 0.972
Negative net radiaton measurements must be multiplied by 1.0198
Measurements:sgp5ebbrE12.b1:
  • Net radiation(net_radiation)
more
sgp30ebbrE12.b1:
  • Net radiation(net_radiation)
  • Surface sensible heat flux(sensible_heat_flux)
  • Surface latent heat flux(latent_heat_flux)
more

Close this window