Start Date | Start Time | End Date | End Time |
---|---|---|---|
11/01/2006 | 0000 | 05/22/2007 | 2347 |
Subject: | NSA/METTWR/C1 - 40m wind sensor heater failure |
DataStreams: | nsamettwr4hC1.b1 |
Description: | The 40m wind direction became frozen at times. The values from the sensor were flat-lined (stdev = 0) much of the time and did not match sensors from other levels. |
Suggestions: | Use wind direction from the 20m level instead. |
Measurements: | nsamettwr4hC1.b1: more
|