DQR ID | Subject | Data Streams Affected |
---|---|---|
D040907.1 | SGP/SIRS/C1/E13 - Incorrect calibration coefficients | sgpsirsC1.00, sgpsirsC1.b1, sgpsirsE13.00, sgpsirsE13.b1, sgpsirs20sC1.a0, sgpsirs20sE13.a0 |
D050106.4 | SGP/SIRS/C1 - Reprocess: UIR/DIR Incorrect calibration coefficients | sgpsirsC1.00, sgpsirsC1.b1 |
D050225.2 | SGP/BRS/C1 - Reprocess: Incorrect Calibration Coefficients | sgpbrsC1.00, sgpbrsC1.b1, sgpbrs20sC1.a0 |
D050322.1 | SGP/BRS/C1 - low downwelling shortwave readings | sgpbrsC1.00, sgpbrsC1.b1, sgpbrs20sC1.a0 |
Start Date | Start Time | End Date | End Time |
---|---|---|---|
08/27/2004 | 1830 | 09/07/2004 | 2130 |
Subject: | SGP/SIRS/C1/E13 - Incorrect calibration coefficients |
DataStreams: | sgpsirsC1.00, sgpsirsC1.b1, sgpsirsE13.00, sgpsirsE13.b1, sgpsirs20sC1.a0, sgpsirs20sE13.a0 |
Description: | After the DIR changeout on 8/27, the DLH measurements at the central facility vary significantly between pyrgeometers by as much as 65 Wm^(-2). It was discovered that the two downwelling pyrgeometers destined for C1 and E13 may have been swapped during installation. The instrument mentor is unsure of applied calibration coefficients during this DQR's time period. Backing out new downwelling longwave irradiances would be difficult in this case. Fortunately, the problem period is less than a fortnight. |
Measurements: | sgpsirsE13.b1:
sgpsirsC1.b1:
sgpsirsC1.00:
sgpsirs20sE13.a0:
sgpsirs20sC1.a0:
sgpsirsE13.00:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
09/27/2004 | 1429 | 01/07/2005 | 1623 |
Subject: | SGP/SIRS/C1 - Reprocess: UIR/DIR Incorrect calibration coefficients |
DataStreams: | sgpsirsC1.00, sgpsirsC1.b1 |
Description: | It appears the datalogger program at SIRS/C1 was automatically updated, unbeknownst to anyone, on 9/27/20041423GMT with an older program with incorrect UIR and DIR calibration coefficients. The correct and incorrect cal coeffs for the UIR and DIR pyrgeometers during this DQR period were: incorrectUIR correctUIR K0 -12.84 -13.00 K1 .2250 0.2573 K2 1.024 1.024 K3 -1.9280 -1.8050 incorrectDIR correctDIR K0 -13.15 -26.89 K1 0.2374 0.2967 K2 1.0260 1.0560 K3 -2.478 -3.3080 |
Measurements: | sgpsirsC1.b1:
sgpsirsC1.00:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
08/05/2004 | 1500 | 12/03/2004 | 1700 |
Subject: | SGP/BRS/C1 - Reprocess: Incorrect Calibration Coefficients |
DataStreams: | sgpbrsC1.00, sgpbrsC1.b1, sgpbrs20sC1.a0 |
Description: | Lightening strike on or near 6/2/2004 took the BRS NIP(31747E6) out of service, on or near 6/15 the NIP was replaced and the datalogger program was changed to reflect the new NIP(31343E6). On 8/5/2004 the DIR (Downwelling longwave) instrument was changed out and a new program was loaded to reflect a new DIR. The new program contained the original installed shortwave instrument calibration coefficients including NIP 31747E6. Thus from 8/5 to when the shortwave instruments were changed out on 12/3 the wrong s/n and calibration factor (i.e. 31747E6) was applied to the actual NIP(31343E6)installed at BRS C1. |
Measurements: | sgpbrs20sC1.a0:
sgpbrsC1.00:
sgpbrsC1.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
04/18/2003 | 0000 | 12/17/2004 | 2030 |
Subject: | SGP/BRS/C1 - low downwelling shortwave readings |
DataStreams: | sgpbrsC1.00, sgpbrsC1.b1, sgpbrs20sC1.a0 |
Description: | Downwelling shortwave (DS) values frequently drop below -10 W/m^2 at night, and are consistently 20-40 W/m^2 less than the calculated downwelling shortwave during the day in clear-sky conditions. Corrective maintenance on 12/17/2004 corrected this offset. It is not clear which CM action corrected the problem since the DS instrument cable was grounded to a new location and the DS ventilator fan was found in poor condition and was replaced. Either of these issues could have led to the problem observed in this instrument. |
Measurements: | sgpbrs20sC1.a0:
sgpbrsC1.00:
sgpbrsC1.b1:
|