Data Quality Reports for Session: 105399 User: wlj Completed: 04/25/2007


TABLE OF CONTENTS

DQR IDSubjectData Streams Affected
D040428.1TWP/SMET/C1 - Poor Performing Sensortwpsmet60sC1.b1
D040824.3TWP/SMET/C1 - Incorrect rainrate equation usedtwpsmet60sC1.b1
D060817.3TWP/SMET/C1 - Reprocess: Barometric Data Changed from hPa to kPatwpsmet60sC1.b1
D061011.2TWP/SMET/C1 - Reprocess: Tipping bucket rain gauge addedtwpsmet60sC1.b1


DQRID : D040428.1
Start DateStart TimeEnd DateEnd Time
04/23/2004000001/19/20051530
Subject:
TWP/SMET/C1 - Poor Performing Sensor
DataStreams:twpsmet60sC1.b1
Description:
On 4/23/2004 condensation was found inside the target area of the ORG lens. A spare was 
sent and installed but did not solve the problem of high background voltage values causing 
rainrate values to be recorded during no rainfall.  Values range anywhere from 0.06 to 
0.12 mm/hr.  

A new Optical Rain Gage was installed on 01/19/2005 @ 13:30 GMT alleviating the high 
background voltage values that lead to consistent rainfall rates of around 0.11 to 0.15 mm/hr 
on a consistent basis.  

The formula used to calculate rainfall rates from the new Optical Rain Gage is:  RR 
(mm/hr) = 25(V^1.87) - 0.15.

Older model formula = 20(V^2) - 0.05

The two formulas result in comparable data.
Measurements:twpsmet60sC1.b1:
  • Precipitation mean(precip_mean)
  • Precipitation maximum(precip_max)
  • Precipitation standard deviation(precip_sd)
  • precipitation minimum(precip_min)


Back To Table of Contents

DQRID : D040824.3
Start DateStart TimeEnd DateEnd Time
08/03/2004030708/17/20042138
Subject:
TWP/SMET/C1 - Incorrect rainrate equation used
DataStreams:twpsmet60sC1.b1
Description:
There are two different Optical Raingages in use at the TWP sites.  The incorrect equation 
was used at this site.  The incorrect equation is (25*(V^1.87)) - 0.15.
The correct equation is (20*(V^2)) - 0.05.  The correct equation was installed.
Measurements:twpsmet60sC1.b1:
  • Precipitation mean(precip_mean)
  • Precipitation maximum(precip_max)
  • Precipitation standard deviation(precip_sd)
  • precipitation minimum(precip_min)


Back To Table of Contents

DQRID : D060817.3
Start DateStart TimeEnd DateEnd Time
10/09/1996000007/13/20062225
Subject:
TWP/SMET/C1 - Reprocess: Barometric Data Changed from hPa to kPa
DataStreams:twpsmet60sC1.b1
Description:
Barometric pressure data was converted from hPa to kPa in order to standardize the 
measurement units among ARM sites and to conform to accepted standard units determined by the 
scientific community.
Measurements:twpsmet60sC1.b1:
  • Atmospheric pressure(atmos_pressure)


Back To Table of Contents

DQRID : D061011.2
Start DateStart TimeEnd DateEnd Time
10/09/1996000009/26/20061438
10/09/1996000010/17/20060000
Subject:
TWP/SMET/C1 - Reprocess: Tipping bucket rain gauge added
DataStreams:twpsmet60sC1.b1
Description:
A tipping bucket rain gauge was added to the TWP.C1 SMET suite of instruments on 20061017. 
 Effective 20060926, two new variables (count and rain amount) were added to the end of 
the twpsmet60sC1.b1 datastream.  Between 9/26 and 10/17, the data for these two variables 
are filled with zeros.  Users should not use the data during this period as the zeros 
are not representative of the rain fall at the site.  When reprocessing of this datastream 
occurs these variables will be added for the 19961009-20060926 and data from 
19961009-20061017 will be filled with -9999 (missing).
Measurements:twpsmet60sC1.b1:
  • Time offset from base_time(base_time)


Back To Table of Contents



END OF DATA