DQR ID | Subject | Data Streams Affected |
---|---|---|
D060425.1 | SGP/EBBR/E27 - Sensible and Latent Heat Fluxes Incorrect | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
D060712.1 | SGP/EBBR/E27 - Field fire burned AEM | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
D060809.1 | SGP/EBBR/E27 - Sensible, Latent, and Average Soil Heat Fluxes Sometimes Incorrect | sgp15ebbrE27.b1, sgp30ebbrE27.b1 |
D060809.2 | SGP/EBBR/E27 - Low Battery Condition | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
D060818.11 | SGP/EBBR/E27 - Most Measurements Suspect | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
D060818.13 | SGP/EBBR/E27 - Battery Voltage Problem - Measurements Incorrect | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
D070809.1 | SGP/EBBR/E27 - Multiplexer #2 failure | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
D080114.3 | SGP/EBBR/E27 - Measurements offscale | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
Start Date | Start Time | End Date | End Time |
---|---|---|---|
03/03/2006 | 0000 | 05/10/2006 | 1130 |
05/25/2006 | 2100 | 06/20/2006 | 1730 |
Subject: | SGP/EBBR/E27 - Sensible and Latent Heat Fluxes Incorrect |
DataStreams: | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
Description: | The left T/RH probe temperature sensor was spiking some of the time during these periods. Therefore, sensible and latent heat fluxes were incorrect during parts of the periods as well. |
Measurements: | sgp5ebbrE27.b1:
sgp30ebbrE27.b1:
sgp15ebbrE27.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
07/11/2006 | 0130 | 07/21/2006 | 1730 |
Subject: | SGP/EBBR/E27 - Field fire burned AEM |
DataStreams: | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
Description: | A fire in the E27 field burned the AEM, making it non-functional. Sensible and latent heat fluxes and gradients were incorrect during this period. |
Measurements: | sgp5ebbrE27.b1:
sgp30ebbrE27.b1:
sgp15ebbrE27.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
05/04/2006 | 1930 | 05/04/2006 | 2200 |
05/05/2006 | 0230 | 05/05/2006 | 0800 |
05/06/2006 | 0430 | 06/20/2006 | 1730 |
Subject: | SGP/EBBR/E27 - Sensible, Latent, and Average Soil Heat Fluxes Sometimes Incorrect |
DataStreams: | sgp15ebbrE27.b1, sgp30ebbrE27.b1 |
Description: | The Soil Heat Flow #1 sensor kept going offscale. Sensible and Latent heat fluxes and the ave_shf were affected and sometimes incorrect. |
Measurements: | sgp30ebbrE27.b1:
sgp15ebbrE27.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
05/31/2006 | 0600 | 06/07/2006 | 1730 |
06/14/2006 | 0500 | 06/20/2006 | 1730 |
Subject: | SGP/EBBR/E27 - Low Battery Condition |
DataStreams: | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
Description: | A low battery condition caused most of the measurements to be incorrect. |
Measurements: | sgp5ebbrE27.b1:
sgp30ebbrE27.b1:
sgp15ebbrE27.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
04/26/2006 | 1830 | 08/17/2006 | 1730 |
Subject: | SGP/EBBR/E27 - Most Measurements Suspect |
DataStreams: | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
Description: | The wrong EBBR program was used at this site. Therefore, most of the measurements are suspect. Note: Mentor reports reprocessing will not correct this problem. |
Measurements: | sgp5ebbrE27.b1:
sgp30ebbrE27.b1:
sgp15ebbrE27.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
08/11/2006 | 1300 | 08/21/2006 | 2330 |
Subject: | SGP/EBBR/E27 - Battery Voltage Problem - Measurements Incorrect |
DataStreams: | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
Description: | Battery voltage was too low much of the time during the period, thus most measurements were incorrect during much of the time period. |
Measurements: | sgp5ebbrE27.b1:
sgp30ebbrE27.b1:
sgp15ebbrE27.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
08/07/2007 | 2130 | 08/13/2007 | 1600 |
08/19/2007 | 1300 | 08/29/2007 | 2130 |
Subject: | SGP/EBBR/E27 - Multiplexer #2 failure |
DataStreams: | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
Description: | A problem with the #2 Multiplexer caused a large number of measurements to be incorrect. Sensible and latent heat fluxes were often affected. |
Measurements: | sgp5ebbrE27.b1:
sgp30ebbrE27.b1:
sgp15ebbrE27.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
12/22/2007 | 1800 | 03/26/2008 | 1730 |
Subject: | SGP/EBBR/E27 - Measurements offscale |
DataStreams: | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
Description: | All J-panel 4 measurements (soil heat flows, net radiation, air temperatures, home signals, pressure, vapor pressure) were sometimes offscale or otherwise incorrect. J-Panel was replaced 20080326 correcting the problem. |
Measurements: | sgp5ebbrE27.b1:
sgp30ebbrE27.b1:
sgp15ebbrE27.b1:
|