DQR ID | Subject | Data Streams Affected |
---|---|---|
D060425.1 | SGP/EBBR/E27 - Sensible and Latent Heat Fluxes Incorrect | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
D060622.2 | SGP/EBBR/E13 - Fluxes Incorrect, AEM Problems | sgp15ebbrE13.b1, sgp30ebbrE13.b1, sgp5ebbrE13.b1 |
D060622.6 | SGP/EBBR/E20 - Net Radiation, Fluxes Too Large | sgp30ebbrE20.b1, sgp5ebbrE20.b1 |
D060809.1 | SGP/EBBR/E27 - Sensible, Latent, and Average Soil Heat Fluxes Sometimes Incorrect | sgp15ebbrE27.b1, sgp30ebbrE27.b1 |
D060809.2 | SGP/EBBR/E27 - Low Battery Condition | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
D060818.11 | SGP/EBBR/E27 - Most Measurements Suspect | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
D060818.8 | SGP/EBBR/E8 - Sensible and Latent Heat Fluxes and Net Radiation Incorrect | sgp15ebbrE8.b1, sgp30ebbrE8.b1, sgp5ebbrE8.b1 |
Start Date | Start Time | End Date | End Time |
---|---|---|---|
03/03/2006 | 0000 | 05/10/2006 | 1130 |
05/25/2006 | 2100 | 06/20/2006 | 1730 |
Subject: | SGP/EBBR/E27 - Sensible and Latent Heat Fluxes Incorrect |
DataStreams: | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
Description: | The left T/RH probe temperature sensor was spiking some of the time during these periods. Therefore, sensible and latent heat fluxes were incorrect during parts of the periods as well. |
Measurements: | sgp5ebbrE27.b1:
sgp15ebbrE27.b1:
sgp30ebbrE27.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
04/30/2006 | 2100 | 05/01/2006 | 1530 |
06/05/2006 | 2330 | 06/06/2006 | 1600 |
06/14/2006 | 2030 | 06/15/2006 | 1430 |
Subject: | SGP/EBBR/E13 - Fluxes Incorrect, AEM Problems |
DataStreams: | sgp15ebbrE13.b1, sgp30ebbrE13.b1, sgp5ebbrE13.b1 |
Description: | The AEM did not function properly, thus sensible and latent heat fluxes were incorrect. |
Measurements: | sgp15ebbrE13.b1:
sgp5ebbrE13.b1:
sgp30ebbrE13.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
06/17/2006 | 0900 | 06/20/2006 | 1915 |
Subject: | SGP/EBBR/E20 - Net Radiation, Fluxes Too Large |
DataStreams: | sgp30ebbrE20.b1, sgp5ebbrE20.b1 |
Description: | Net Radiation was way too large because of water in the bottom dome. This resulted in the sensible and latent heat fluxes being too large also. |
Measurements: | sgp5ebbrE20.b1:
sgp30ebbrE20.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
05/04/2006 | 1930 | 05/04/2006 | 2200 |
05/05/2006 | 0230 | 05/05/2006 | 0800 |
05/06/2006 | 0430 | 06/20/2006 | 1730 |
Subject: | SGP/EBBR/E27 - Sensible, Latent, and Average Soil Heat Fluxes Sometimes Incorrect |
DataStreams: | sgp15ebbrE27.b1, sgp30ebbrE27.b1 |
Description: | The Soil Heat Flow #1 sensor kept going offscale. Sensible and Latent heat fluxes and the ave_shf were affected and sometimes incorrect. |
Measurements: | sgp15ebbrE27.b1:
sgp30ebbrE27.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
05/31/2006 | 0600 | 06/07/2006 | 1730 |
06/14/2006 | 0500 | 06/20/2006 | 1730 |
Subject: | SGP/EBBR/E27 - Low Battery Condition |
DataStreams: | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
Description: | A low battery condition caused most of the measurements to be incorrect. |
Measurements: | sgp5ebbrE27.b1:
sgp15ebbrE27.b1:
sgp30ebbrE27.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
04/26/2006 | 1830 | 08/17/2006 | 1730 |
Subject: | SGP/EBBR/E27 - Most Measurements Suspect |
DataStreams: | sgp15ebbrE27.b1, sgp30ebbrE27.b1, sgp5ebbrE27.b1 |
Description: | The wrong EBBR program was used at this site. Therefore, most of the measurements are suspect. Note: Mentor reports reprocessing will not correct this problem. |
Measurements: | sgp5ebbrE27.b1:
sgp15ebbrE27.b1:
sgp30ebbrE27.b1:
|
Start Date | Start Time | End Date | End Time |
---|---|---|---|
06/23/2006 | 0130 | 06/27/2006 | 1730 |
Subject: | SGP/EBBR/E8 - Sensible and Latent Heat Fluxes and Net Radiation Incorrect |
DataStreams: | sgp15ebbrE8.b1, sgp30ebbrE8.b1, sgp5ebbrE8.b1 |
Description: | The net radiometer top dome was broken and water had gotten into it. Sensible and latent heat fluxes and net radiation were therefore incorrect. |
Measurements: | sgp15ebbrE8.b1:
sgp5ebbrE8.b1:
sgp30ebbrE8.b1:
|